Earth Leakage Circuit Breaker QuickConnect 4-Pole Type A 30mA 25A IP20 Hager
Watch this product and we will notify you once it is back in stock.
Earth Leakage Circuit Breaker QuickConnect 4-Pole Type A 30mA 25A IP20 Hager
Description
Earth Leakage Circuit Breaker Type A, 4-Pole with 30mA Fault Current and QuickConnect. With the quick connection technology "QuickConnect," the busbar can be pressed in after the other cables are installed. The screw on the Earth Leakage Circuit Breaker only affects the lift clamp and not the busbar, meaning you can easily add wires to the next row before connecting the busbar. If a component needs to be replaced on the DIN rail, it can be done without affecting other components. All Earth Leakage Circuit Breakers are surge current-resistant, meaning they are protected from unnecessary disconnections in the power grid due to transients or what we call spikes. All Type A Earth Leakage Circuit Breakers are DC pulse-sensitive and can interrupt the main circuit in case of non-sinusoidal fault currents. The Earth Leakage Circuit Breakers come with a transparent protective cover for labeling. Flexible conductors can be connected under the busbar with a screw connection. The busbar is simply pressed in, and there is no need for re-tightening. Note: Hager's busbar KDNxxx must be used. The functionality of the Earth Leakage Circuit Breaker should be regularly tested every 6 months using the test button on each device. Minimum temperature: -25ºC.
Technical Information
- Installation depth: 70 mm
- Mounting method: DIN rail
- Rated current: 25 A
- Width in number of module spaces: 4
- Leakage current type: A
- Rated voltage: 400 V
- Protection class (IP): IP20
- Number of poles: 4
- Voltage type: AC
- Impulse protection rated voltage Uimp: 4 kV
- Connectable conductor area solid: 1-25 mm²
- Surge current capacity: 0.25 kA
- Connectable conductor area stranded: 1-16 mm²
- Rated residual current: 0.03 A
- Short-circuit withstand strength (lcw): 6 kA
- Ambient temperature during operation: -25-40 °C
- Rated insulation voltage: 500 V
- Pollution degree: 2
- Frequency: 50 Hz
Specifications
- REACH - Contains candidate substances: Lead
- REACH Date: 2022-11-23
- REACH Information requirement: Yes
- Additional devices possible: Yes